4.10 S9 THERMAL MODEL
To illustrate the Voltage Dependent Overload Curve feature, the thermal limits shown in Figure 4–13: THERMAL LIMITS
FOR HIGH INERTIAL LOAD on page 4–57 will be used.
1.
Construct a custom curve for the running overload thermal limit. If the curve does not extend to the acceleration ther-
mal limits, extend it such that the curve intersects the acceleration thermal limit curves. (see CUSTOM CURVE below).
2.
Enter the per unit current value for the acceleration overload curve intersect with the custom curve for 80% voltage.
Also enter the per unit current and safe stall protection time for 80% voltage (see ACCELERATION CURVE below).
3.
Enter the per unit current value for the acceleration overload curve intersect with the custom curve for 100% voltage.
Also enter the per unit current and safe stall protection time for 100% voltage (see ACCELERATION CURVE below)
GE Power Management
1000
900
800
700
600
500
400
4
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
1
2
3
4-58
489
VOLTAGE DEPENDENT OVERLOAD
(CUSTOM CURVE)
Acceleration intersect @ 80% V
Acceleration Intersect @ 100% V
4
5
6
7
MULTIPLES OF FULL LOAD AMPS
Figure 4–14: VOLTAGE DEPENDENT OVERLOAD CURVES
489 Generator Management Relay
GE Power Management
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
8
1
2
808827A2.CDR
4 SETPOINT PROGRAMMING
489
VOLTAGE DEPENDENT OVERLOAD
(ACCELERATION CURVES)
489 Custom Curve
3
4
5
6
MULTIPLES OF FULL LOAD AMPS
GE Power Management
7
8
808828A2.CDR