GE 489 Instruction Manual page 142

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

5.8 DIAGNOSTICS
DATE ENTRY WAS NOT COMPLETE:
sage appears and the new value will not be stored if the
entered. Another attempt will have to be made with the complete information.
DATE ENTRY WAS OUT OF RANGE:
month).
TIME ENTRY WAS NOT COMPLETE:
appears and the new value will not be stored if the
entered. Another attempt will have to be made with the complete information.
TIME ENTRY WAS OUT OF RANGE:
NO TRIPS OR ALARMS TO RESET:
RESET PERFORMED SUCCESSFULLY:
that caused these trips and/or alarms are no longer present), then this message appears when a RESET is performed,
indicating that all trips and alarms have been cleared.
ALL POSSIBLE RESETS HAVE BEEN PERFORMED:
cleared (that is, the conditions that caused some of these trips and/or alarms are still present), then this message
appears when a RESET is performed, indicating that only trips and alarms that could be reset have been reset.
CONDITION IS PRESENT RESET NOT POSSIBLE:
condition that caused these trips and/or alarms is still present), then this message appears when the
pressed.
ARE YOU SURE? PRESS [ENTER] TO VERIFY:
sible, this message appears to verify the operation. If
reset will be performed.
5
PRESS [ENTER] TO ADD DEFAULT MESSAGE:
entered anywhere in the actual value message structure. This message prompts the user to press
default message. To add a new default message,
DEFAULT MESSAGE HAS BEEN ADDED:
DEFAULT MESSAGE LIST IS FULL:
list when 20 messages are already assigned. To add a new message, one of the existing messages must be removed.
PRESS [ENTER] TO REMOVE MESSAGE:
in the
S1 489 SETUP \ DEFAULT MESSAGES
default message. To remove the default message,
DEFAULT MESSAGE HAS BEEN REMOVED:
DEFAULT MESSAGES 6 of 20 ARE ASSIGNED:
entered, notifying the user of the number of default messages assigned.
INVALID SERVICE CODE ENTERED:
points page.
KEY PRESSED HERE IS INVALID:
while viewing actual values). This message appears if a keypress has no current function.
DATA CLEARED SUCCESSFULLY:
[.] KEY IS USED TO ADVANCE THE CURSOR:
time a setpoint requiring text editing is viewed. If the setpoint is not altered for 1 minute, this message flashes again.
This message will indicate when the top of a page has been reached.
TOP OF PAGE:
BOTTOM OF PAGE:
This message will indicate when the top of subgroup has been reached.
TOP OF LIST:
This message will indicate when the bottom of a subgroup has been reached.
BOTTOM OF LIST:
NO ALARMS ACTIVE:
this message will appear.
5-28
Since the
DATE
Appears if an invalid entry is made for the
Since the
TIME
Appears if an invalid entry is made for the
Appears if the
If all trip and alarm features that are active can be cleared (that is, the conditions
If no trip and alarm features that are active can be cleared (that is, the
If the
Appears if the decimal [.] key, immediately followed by the
Appears anytime a new default message is added to the default message list.
Appears if an attempt is made to add a new default message to the default message
Appears if the decimal [.] key, immediately followed by the
setpoint page. This message prompts the user to press
Appears anytime a default message is removed from the default message list.
Appears anytime the
Appears if an invalid code is entered in the
Under certain situations, certain keys have no function (for example, any number key
Confirms that data is reset in the
Appears immediately to prompt the use of the [.] key for cursor control any-
This message will indicate when the bottom of a page has been reached.
If an attempt is made to enter the Alarm Status message subgroup, but there are no active alarms,
489 Generator Management Relay
setpoint has a special format (entered as MM/DD/YYYY), this mes-
key is pressed before all of the information has been
ENTER
setpoint has a special format (entered as HH/MM/SS.s), this message
key is pressed before all of the information has been
ENTER
TIME
key is pressed when there are no trips or alarms present.
RESET
If only some of the trip and alarm features that are active can be
key is pressed and resetting of any trip or alarm feature is pos-
RESET
is pressed again while this message is displayed, the
RESET
must be pressed while this message is being displayed.
ENTER
must be pressed while this message is being displayed.
ENTER
S1 489 SETUP \ DEFAULT MESSAGES
S1 489 SETUP \ CLEAR DATA
5 ACTUAL VALUES
(for example, 15 entered for the
DATE
(for example, 35 entered for the hour).
RESET
ENTER
to add a new
ENTER
key, is entered
ENTER
to remove a
ENTER
setpoint page is
S12 489 TESTING \ FACTORY SERVICE
setpoints page.
GE Power Management
key is
key, is
set-