10.3.3 HMI as feedback of the local push button
operations
As consequence of the operations described in the section 8.2,
when the Z or S buttons are released, the feedback of the
executed operation is displayed in the bottom of the LCD
(same position as per diagnostic messages):
Message
Description
! Oper Done
The push button operation has been successfully executed
! Proc Too
The Pressure measured in input is too low and not
Low
acceptable for the requested operation
! Proc Too
The Pressure measured in input is too high and not
High
acceptable for the requested operation
! New URV
The Zero (Z) operation cannot be accepted because the
Error
URV would be shifted outside the Upper Sensor limit
The Span (S) operation cannot be accepted because the
! Span Error
new URV would be too close to the LRV and their
difference lower than the Minimum Span value
The push button operation has been refused because the
! Oper
Write Protection is enabled with the hardware button or in
Disabled
PB_WRITE_LOCKING or because the Local Operation is
disabled in the PB_LOCAL_OP_ENA
10.3.4 HMI as configuration tool
The HMI can be used to read and change the display
configuration through a dedicated menu accessible by using
the 4 HMI buttons. To access the functionality of the HMI an
activation procedure needs to be carried out.
LCD (L1 option) activation considerations
Gain access to the display by unscrewing the windowed cover.
Please observe the Hazardous area prescription before
proceeding with the cover removal. For activation, see following
instructions.
TTG (L5 option) activation considerations
The TTG technology allows the user to activate the keypad on
the HMI without the need of opening the windowed cover of
the transmitter. The capacitive pick-ups will detect the
presence of your finger in front of the respective button
activating the specific command.
At the transmitter power-on the HMI automatically calibrate its
sensitivity, it is mandatory for the proper functioning of the TTG
HMI that the cover is properly tightened at power-on.
In case the cover has been removed to access the
communication board, it is recommended to power off and
power-on again the transmitter once the windowed cover has
been set in place and properly tightened.
36 OI/266/PB-EN Rev. E | 2600T Series Pressure transmitters
10.3.5 Activation procedure for TTG (L5) and LCD (L1)
1.
Press the (2) and (3) keys together for 3 seconds until a
special symbol appears in the low left corner of the
display
2.
Press the (4) key
3.
The HMI enter in the configuration menus
The keys (1), (4), (2) and (3) are available for the
menu-controlled configuration.
4.
The menu/submenu name is displayed above in the LCD
display.
5.
The number/line of the currently selected menu item is
displayed in the upper right of the LCD display.
6.
A scroll bar is located on the right edge of the LCD
display which shows the relative position of the currently
selected menu item within the menu.
7.
Both of the keys (1) and (4) can have various functions.
The meaning of these buttons is displayed below in the
LCD display above the respective button.
8.
You can browse through the menu or select a number
within a parameter value using both keys (2) and (3).
The button (4) selects the desired menu item.
Figure 43: Display keypad
Button (1) functionalities
Exit
Back
Cancel
Next
Button (4) functionalities
Select
Edit
Ok
10 HMI Local Indicator
Meaning
Exit menu
Back one submenu
Exit without saving the selected parameter
value
Select next position for entering numerical
values or letters
Meaning
Select submenu/parameter
Edit parameter
Save selected parameter and display
stored parameter value