6.2
List of errors (F-00 ... F-97)
No.
Name
Response
00
No error
01
Over-current
Immediate
switch-off
03
Ground fault
Immediate
switch-off
04
Brake chopper
Immediate
switch-off
06
Supply system
Immediate
phase failure
switch-off
(only with
three-phase
inverter)
07
DC-link over-
Immediate
voltage
switch-off
08
Speed monitor-
Immediate
ing
switch-off
10
ILLOP
Emergency
stop
Operating Instructions – MOVITRAC® 07
List of errors (F-00 ... F-97)
Possible cause
Short circuit on output
Output switching
Motor too large
Defective output stage
Ramp limit (P138) switched off
Ground fault on motor
Ground fault on inverter
Ground fault in the motor lead
Over-current (see F-01)
Regenerative power excessive
Braking resistor circuit interrupted
Short circuit in braking resistor cir-
cuit
Excessively high braking resis-
tance
Brake chopper defective
Ground fault
Phase fault
DC link voltage too high
Ground fault
Current controller is operating at the
setting limit due to:
mechanical overload
phase failure in supply system
phase failure in motor
Maximum speed for VFC operating
mode exceeded
Incorrect command during running
of program
Incorrect conditions during running
of program
Function not in inverter / not imple-
mented
Operation and Service
Action
Rectify the short circuit
Only switch when output stage
inhibited
Connect a smaller motor
Call SEW Service for advice if the
fault still cannot be reset
Ramp limit (P138 = YES)
Replace the motor
Replace the MOVITRAC
Rectify the ground fault
See F-01
Extend deceleration ramps
Check connecting harness for
braking resistor
Rectify the short circuit
Check technical data of braking
resistor
Replace the MOVITRAC
Rectify the ground fault
Check supply system lead
Extend deceleration ramps
Check connecting harness for
braking resistor
Check technical data of braking
resistor
Rectify the ground fault
Reduce load
Increase delay time setting P501
Check current limitation
Extend deceleration ramps
Check supply system phases
Check motor feeder and motor
Reduce maximum speed
Check program
Check program structure
Use another function
6
®