6.2
List of errors (F-00 ... F-97)
No.
Name
Response
00
No error
01
Over-current
Immediate
switch-off
03
Ground fault
Immediate
switch-off
04
Brake chopper
Immediate
switch-off
06
Supply system
Immediate
phase failure
switch-off
(only with
three-phase
inverter)
07
DC-link over-
Immediate
voltage
switch-off
08
Speed monitor-
Immediate
ing
switch-off
10
ILLOP
Emergency
stop
Operating Instructions – MOVITRAC® 07
List of errors (F-00 ... F-97)
Possible cause
•
Short circuit on output
•
Output switching
•
Motor too large
•
Defective output stage
•
Ramp limit (P138) switched off
•
Ground fault on motor
•
Ground fault on inverter
•
Ground fault in the motor lead
•
Over-current (see F-01)
•
Regenerative power excessive
•
Braking resistor circuit interrupted
•
Short circuit in braking resistor cir-
cuit
•
Excessively high braking resis-
tance
•
Brake chopper defective
•
Ground fault
Phase fault
•
DC link voltage too high
•
Ground fault
Current controller is operating at the
setting limit due to:
•
mechanical overload
•
phase failure in supply system
•
phase failure in motor
Maximum speed for VFC operating
mode exceeded
•
Incorrect command during running
of program
•
Incorrect conditions during running
of program
•
Function not in inverter / not imple-
mented
Operation and Service
Action
•
Rectify the short circuit
•
Only switch when output stage
inhibited
•
Connect a smaller motor
•
Call SEW Service for advice if the
fault still cannot be reset
•
Ramp limit (P138 = YES)
•
Replace the motor
•
Replace the MOVITRAC
•
Rectify the ground fault
•
See F-01
•
Extend deceleration ramps
•
Check connecting harness for
braking resistor
•
Rectify the short circuit
•
Check technical data of braking
resistor
•
Replace the MOVITRAC
•
Rectify the ground fault
Check supply system lead
•
Extend deceleration ramps
•
Check connecting harness for
braking resistor
•
Check technical data of braking
resistor
•
Rectify the ground fault
•
Reduce load
•
Increase delay time setting P501
•
Check current limitation
•
Extend deceleration ramps
•
Check supply system phases
•
Check motor feeder and motor
•
Reduce maximum speed
•
Check program
•
Check program structure
•
Use another function
6
®
07
®
07
45
Need help?
Do you have a question about the MOVITRAC 07 and is the answer not in the manual?