Remedial Measures Table 5 - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Alarm, error, and system messages
10.4 Fault correction
10.4.6

Remedial measures table 5

Fault profile (symptoms)
Zero point displaces sporadically
(> 3%).
The device function has completely
failed: No representation on the
display either.
Fault table 5
See also
Repair/Upgrading (Page 238)
234
Possible cause(s)
Impact or shock loads result in
accelerations so high that the fric-
tion clutch moves, e.g. due to "va-
por shocks" in vapor lines.
Electrical auxiliary power supply is
not adequate.
In case of very high continuous
loads due to vibrations (oscilla-
tions):
Screws of the electrical connecting
terminals may be loosened.
Electrical connecting terminals
and/or electronic components may
be knocked out.
Corrective measures
Rectify the causes for shock loads.
Re-initialize the position controller.
Check the electrical auxiliary power
supply.
Tighten the screws firmly and se-
cure using sealing wax.
Repair
For prevention: Install the positioner
on the damping pads.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12