9.4.2.14

'44.AFCT' Alarm function

Possible settings:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
See representation below
This parameter can be used to determine the value at which going
above or below a given offset or angle will result in a message.
The triggering of alarms (limits) is relative to the MPOS scale.
Alarms are signaled through the alarm module. In addition, alarms
can also be read out over the HART communicator (optional).
The direction of action of the binary outputs can be adjusted from
"High active" to "Low active" for the next system.
OFF
Direction of action and hysteresis
Parameterizing/addressing
9.4 Description of parameters
Alarm module
Examples
A1
A1 = 48
AFCT = MIN / MAX
A2 = 52
Way =45
Active
Way =50
Way =55
A1 = 48
AFCT = -MIN / -MAX
A2 = 52
Way =45
Way =50
Active
Way =55
Active
A1 = 52
AFCT = MIN / MAX
A2 = 48
Way =45
Active
Way =50
Active
Way =55
A1 = 52
AFCT = -MIN / -MAX
A2 = 48
Way =45
Way =50
Way =55
Active
A2
Active
Active
Active
Active
Active
Active