Commissioning
7.6 Commissioning part-turn actuators
See also
Pneumatic connection (Page 100)
External position detection (Page 48)
7.6.2

Automatic initialization of part-turn actuators

Requirements
The following conditions must be fulfilled before activating the automatic initialization:
1. The travel range of the actuator can be passed through completely.
2. The actuator shaft is at a central position.
Initializing the part-turn actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
until the display shows the following:
2. Use the
shows the following:
132
button to change from linear actuator to part-turn actuator until the display
button for at least 5 seconds
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
. The settings