Safety, approvals, EMC

7.2 Test voltage

7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals and PE together
Test (C)
● Connect the output terminals with one another and measure with respect to PE
Table 7- 1
Test voltage
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA
42
Test voltage diagram
Test time
60 s
60 s
1 s
1 s
1 s
1 s
Prim ↔ sec (A)
4200 V DC
3000 VAC
2200 V DC
1500 VAC
2200 V DC
1500 VAC
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
Prim ↔ PE (B)
2200 V DC
1500 VAC
2200 V DC
1500 VAC
2200 V DC
1500 VAC
Sec ↔ PE (C)
700 V DC
500 VAC
500 V DC
350 VAC
500 V DC
350 VAC