ABB 07 MK 92 R1161 Operating Manual page 16

Intelligent decentralized automation system communication module advant controller 31
Table of Contents

Advertisement

7.2.6.5
LED displays
LEDs for operating and error displays:
– Supply voltage present (Supply)
– Fatal or serious error occurred (ERR)
– Application program processing running (RUN)
Configurable LEDs for diagnosis: LED1...LED4
7.2.6.6
Mechanical data
Mounting on DIN rail
Fastening by screws
Width x height x depth
Wiring method
Weight
Dimensions for mounting
The device is 85 mm deep. The interface connectors COM3 and COM4 are set deeper so that the mounting
depth required does not become any larger even with detachable interface cables. If, however, a DIN rail is used,
the mounting depth is increased by the overall depth of the rail.
Fig. 7.2-15: Dimensions of the communication module 07 MK 92,
front view, the dimensions for assembly bore holes are printed in bold
7.2.6.7
Mounting hints
Mounting position
Cooling
2
07 MK 92 R1161
1 green LED
1 red LED
1 green LED
4 yellow LEDs
in accordance with DIN EN 50022–35, 15 mm deep.
The DIN rail is located in the middle between the upper
and the lower edges of the module.
using 4 M4 screws.
140 x 120 x 85 mm
by removeable terminal blocks with screw-type
450 g
see the following drawing
120
20
94
75
94
vertical, terminals above and below
The natural convection cooling must not be hindered by
cable ducts or other material mounted in the switch-
gear cabinet.
7.2-14
terminals, max. 2.5 mm
5
Hardware
2
All dimensions in mm.