ABB Endura AZ series User Manual page 21

Integral and remote transmitter, combustion oxygen monitor
Table of Contents

Advertisement

Endura AZ series integral and remote transmitter
Combustion oxygen monitor
Factory-made
connections
(at probe inner
terminal connectors)
*Cut the screen, screen foil and drain at probe head back and isolate only –
do not connect at probe
**Connect drain from 6-core cable at transmitter to the transmitter internal earth stud only –
do not connect to transmitter terminal SCN connector or transmitter external earth
Fig. 4.7 Remote Transmitter to Remote AZ25 Probe Connections
IM/AZ20E–EN Rev. F
Endura AZ25 probe
Endura AZ25 remote transmitter
T/C +
T/C –
Cell +
Cell –
ACJC
ACJC
Screen / drain of 6-core
sensor cable at Endura
AZ25 probe cut back and
isolated*
Terminal connections at
Endura AZ25 remote transmitter
Cell + (Red)
Cell – (Black)
ACJC (Orange)
ACJC (Blue)
T/C + (Green)
T/C – (White)
– NOT USED
SCN (Screen)
Connect drain at Endura AZ25 transmitter
end to transmitter internal earth stud only**
4 Electrical Installation
Green
White
Red
Black
Orange
Blue
6-Core sensor
cable wire colors
Refer to Table 4.4
for wire colors
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Endura az25Endura az20Endura az10