6 Operation

Locking:
1. Close the door.
2. Locking as PLC program (e.g. via signal from push button).
Unlocking:
1. Unlocking as PLC program (e.g. via signal from push button, or automatically when the machine/process
cycle is ended as it is supposed to).
2. Open the door.

LED indication

LED
LED on Magne
(Magne 4)
LED on Magne
(Magne 3 and 4)
2TLC172315M0201, rev K
Monday, May 07, 2018 10:51:13 AM
Indication
Green
Green–Red (blinking)
Green–Red (rapid
blinking)
Red
Blue (rapid blinking)
Blue (slow blinking)
Blue
Description
Eva close, safety circuit closed (door closed)
Eva close, safety circuit broken earlier (door closed)
Eva is within 2 mm of max sensory distance (door closed)
Eva remote, safety circuit broken (door open)
Overcurrent signaled on attempted locking.
Lock signal but Magne not detecting the anchor plate.
Magne is locked.