3.4.5.12.
34
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Scale
Default: None
Common
Update Rate
0...60000
Default: 0

Integer status (INS)

Information in the following table applies also to the Internal INS data object.
Table 3.4.5.12-1 Configurable INS properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
INS
Class
Addresses
Address
0...65535
Default: 0
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Scale
Default: None
Common
Update Rate
0...60000
Default: 0
Description
Scale used with indication value.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Description
Common data class according to IEC
61850.
Indication address.
Data format.
Scale used with indication value.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.