Node Status Data (128 bits)
This data consists of one bit per slave device, with bit position
indicating the address. For example slave address 2 is indicated by
bit 1 (first bit is bit 0).
Node Status
Bit =
0
1
14
PACSystems* RX3i CANopen Master Module Quick Start GFK-2837
The device is either not configured, or
configured and not exchanging data. Loss of
or inactive communication between the
master and the slave device.
Failed data path.
PDO Counter Timeout parameter has been
exceeded.
Note: If any slave node status bit is 0, the all
slaves healthy module status bit will also
be 0.
The slave is configured and is exchanging data.
Definition