S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
250
04
Programmed channel type
(3 to 6) for AI module type 13
to 16 is wrong
Additional info. 1:
Module address ("BG")
Additional info. 2:
Channel No. ("KN")
Additional info. 3:
Channel type from
configuration DB
250
05
Wrong call parameter for
FB ANEI:
Individual scanning of AI 463
not permissible
Additional info. 1:
Module address ("BG")
Additional info. 2:
Channel No. ("KN")
250
06
QVZ during access to analog
value: I/O module error
Additional info. 1:
Module address ("BG")
Additional info. 2:
Channel No. ("KN")
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 14
Configuration error
Initial module address,
decimal display
Channel No. used, decimal display
Channel type configured for this
channel, decimal display
Error group No. 12
Programming error:
-
Invalid call parameter for FB ANEI
Initial module address,
decimal display
Channel No. used, decimal display
Error group No. 19
-
AI module defective
-
Channel defective
-
IM306 defective
Initial module address,
decimal display
Channel No. used, decimal display
PLC Error Messages
Remedy
Configuration error
Warm restart:
1. Stop/Run
-
Change call parameter
Set cyclical scanning:
EINZ: KF 0
Warm restart:
1. Stop/Run
-
Replace module
-
Replace IM306
Warm restart:
1. Stop/Run
B-75