PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
32
01
QVZ during writing of CH DQ
module: I/O module error
Additional info. 1:
CH DQ No.
32
02
QVZ during reading of DI
module:
I/O module error
Additional info. 1:
DI word No.
32
03
CPU error
Additional info. 1:
DI word No.
B-30
Possible Cause
Error group No. 19
Event-driven DI module test:
-
CH DQ module not available
-
CH DQ module defective
-
CH DQ module in IM 306
wrongly addressed
-
IM306 defective
Word No. of the erroneous module,
decimal display
Error group No. 19
Event-driven DI module test:
-
DI module not available
-
DI module defective
-
DI module in IM306
wrongly addressed
-
IM306 defective
Word No. of the erroneous module,
decimal display
Error group No. 13
Event-driven DI module test:
Wrong type identifier in the
reference table
-
CPU error
Word No. with wrong type identifier,
decimal display
S5-115F Manual
Remedy
-
Plug in module
(if necessary, change
configuration)
-
Replace module
-
Check addressing
-
Replace IM306
Warm restart:
1. Stop/Run
-
Plug in module
(if necessary, change
configuration)
-
Replace module
-
Check addressing
-
Replace IM306
Warm restart:
1. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02