Fuses

gG and aR fuses for protection against short-circuit in the input power cable or drive
are listed below. Either fuse type may be used if it operates rapidly enough.

Frame sizes R2 to R4

Check from the fuse time-current curve that the operating time of the fuse is
below 0.5 seconds. The operating time depends on the supply network impedance
and the cross-sectional area and length of the supply cable. The short-circuit current
can be calculated as shown below in section
Note 1: See also Planning the electrical installation:
UL recognized fuses, see
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
ACS800-04
size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0001-2
-0002-2
-0003-2
-0004-2
-0005-2
-0006-2
-0009-2
-0011-2
-0016-2
-0020-2
Three-phase supply voltage 380 V, 400 V or 415 V
-0003-3
-0004-3
-0005-3
-0006-3
-0009-3
-0011-3
-0016-3
-0020-3
-0023-3
-0025-3
-0030-3
-0035-3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
NEMA data
on page 103.
Input
2
current
A
A
s
4.4
10
483
5.2
10
483
6.7
10
483
9.3
16
993
12
16
993
16
20
1620
23
25
3100
31
40
9140
40
50
15400
51
63
21300
4.7
10
483
6.0
10
483
7.9
10
483
10
16
993
13
16
993
17
20
1620
23
25
3100
32
40
9140
38
50
15400
42
50
15400
53
63
21300
56
63
21300
Frame sizes R5 and
Thermal overload and short-circuit
Fuse
V
Manufacturer
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
95
R6.
protection. For
Type
IEC size
OFAF000H10
000
OFAF000H10
000
OFAF000H10
000
OFAF000H16
000
OFAF000H16
000
OFAF000H20
000
OFAF000H25
000
OFAF000H40
000
OFAF000H50
000
OFAF000H63
000
OFAF000H10
000
OFAF000H10
000
OFAF000H10
000
OFAF000H16
000
OFAF000H16
000
OFAF000H20
000
OFAF000H25
000
OFAF000H40
000
OFAF000H50
000
OFAF000H50
000
OFAF000H63
000
OFAF000H63
000
Technical data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04Acs800

Table of Contents