E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
Alarm
Alarm Name In Panel
Code
4025
LOCAL DISABLED
4026
AUTO DISABLED
4027
COMM CONFIG ERR
4028
FBA PAR CONF
4029
DRIVE FAULTED
Alarm
Alarm is displayed if
MODE LOCK (16.29)
is set to AUTO MODE
and the Hand or Off
key is pressed
This alarm is displayed
if MODE LOCK (1629)
is set to LOCAL MODE
and the Auto key is
pressed.
Alarm is displayed if
E-Clipse parameters
the drive and bypass
5002(BP MAC ID) &
MAC addresses are
5302 (DV MAC ID) are
equal or invalid.
set to the same value
Non embedded
fieldbus has detected
an error in Group 51
parameters
The drive is faulted.
Possible Cause
Corrective Action
Change MAC address
to unique values
Verify Group 51
parameters
Reset drive
Diagnostics and Troubleshooting
83