E-Clipse Bypass Configurations for ACH550 Drives
Group 53
Code
Name
5319
DV PAR 19
...
...
5320
DV PAR 20
Group 54
Code
Name
5401
DATA IN 1
...
...
5409
DATA IN 9
Group 55
Code
Name
5501
DATA OUT 1
...
...
5510
DATA OUT10
Group 98
Code
Name
9802
COMM PROT
SEL
Group 99
Code
Name
9902
B.P. MACRO
Resolution
Range
hex
0x0000 - 0xFFFF
Resolution
Range
1
0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1
(ABBDP)
6 = Actual Value 2
(ABBDP)
10001 - 19999 = Bypass
parameter index
+10000
Resolution
Range
1
0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1
(ABBDP)
6 = Actual Value 2
(ABBDP)
10001 - 19999 = Bypass
parameter index
+10000
Resolution
Range
1
0=NOT SEL
1=STD MODBUS
2=N2
3=FLN
4=EXT FBA
5=BACNET
Resolution
Range
1
1 = HVAC DEFAULT
2 = DAMPER
3 = RETROFIT
4 = SMOKE CONTROL
Default
Description
0x0000
Default
Description
—
Figure module support. Specifies
addresses of parameters to be
read from the drive (IN to
network). Only for modules that
support the cyclic low scanner
function.
Default
Description
—
Figure module support. Specifies
addresses of parameters to be
read from the drive (OUT to
network). Only for modules that
support the cyclic low scanner
function.
Default
Description
0
This parameter functions in place
of drive parameter 98.02 which
must be set to Modbus in E-
Clipse Bypass system. User
fieldbus is set at E-Clipse panel.
Default
Description
1
Select bypass macro. Predifined
set of parameter values for
certain application is loaded in
use.
Parameter Descriptions
65