Commissioning

7.6 Commissioning part-turn actuators

Aborting the manual initialization process
1. Press the
"Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
software status is displayed. After releasing the
mode". The positioner is not initialized.
7.6
Commissioning part-turn actuators
7.6.1

Preparing part-turn actuators for commissioning

Note
Setting of the adjustment angle
The usual adjustment angle for part-turn actuators is 90°.
● Set the transmission ratio selector in the positioner to 90°.
Requirements
The following conditions must be fulfilled before activating the initialization:
1. You have installed the positioner for the part-turn actuators using the suitable mounting kit.
2. You have connected the actuator and the positioner to the pneumatic lines.
3. Pneumatic auxiliary power is supplied to the positioner.
4. The positioner has been connected to a suitable current or voltage source.
122
button. The display shows the "5.INITM" parameter. The positioner is in the
button for at least 5 seconds. The
button, the positioner is in "P manual
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC