Replacing the rechargeable
battery
Location of the rechargeable
battery
Before replacement
How to replace the
rechargeable battery
System Manual
C79000-B8576-C199-03
The rechargeable battery is situated in the right-hand fan subassembly.
Caution
Do not place the rechargeable battery in contact with fire or heat
and do not short-circuit it.
The rechargeable battery must not be destroyed or disassembled.
Nickel-cadmium batteries contain an alkali electrolyte which can
harm the skin and damage clothing. If your skin or your eyes
make contact with the electrolyte, rinse immediately with clean
water and consult a doctor.
If you operate your power supply with a filter, you must first release
the filter subdrawer and pull it out before dismantling the right-hand
fan and replacing the rechargeable battery (see section entitled
"Replacing the filter mat".
The rechargeable battery can be replaced during operation. Proceed as
follows:
Step
Action
1
Insert a screwdriver (DIN 5265, blade width
3.5-6.5 mm) into the right-hand unlock fan opening.
2
Swing the right-hand fan subassembly out (by placing
your finger in the round opening on the underside at the
front and pulling downwards).
Result:"Fan 3" LED indicates failure of the right-hand fan,
and the other two fans operate at increased speed.
3
Slacken the screws on the bottom of the fan subassembly
and pull out the rechargeable battery.
4
Disconnect the connecting cable of the rechargeable battery.
5
Connect the cable to the new rechargeable battery.
Important
Ensure correct polarity (red terminal on plus, black
terminal on minus, see figure "Replacing the rechargeable
battery in the fan subassembly").