Panasonic AFPE224300 User Manual page 93

Fp-e series panel mounted controller
Hide thumbs Also See for AFPE224300:
Table of Contents

Advertisement

Notes:
1. The points for the timer and counter can be changed by the setting of System register No.5. The
number given in the table above are the numbers when System register No. 5 is at its default setting.
2. There are two unit types;
the hold type that saves the conditions that exist just before turning the power off or changing from the
RUN mode to PROG. mode, and the non-hold type that resets them.
These areas can be specified as hold type or non-hold type by setting system register.
For the FP-e, that area is fixed and allotted the numbers as shown in the table below. For the FP-e
with clock/calendar function type, the selection of hold type and non-hold type can be changed by the
setting of system register.
3. The number of points noted above is the number reserved in the system. For the actual number of
points available for use, refer to "I/O Allocation" in Appendix A.
4. Double words cannot be specified with FPWIN GR.
Hold type and non-hold type areas
Model
Timer
Non-hold type
Counter
Hold type
Non-hold type
Internal
relay
Hold type
Data
Non-hold type
register
Hold type
Notes:
1. When a battery is installed in a calendar timer type FP-e, the areas above can be changed using the
system register.
If a battery is not installed, the data cannot be stored even when the settings are changed using the
system register.
2. Use the following methods for holding the SV data:
1. Set the transfer instruction for the special data register (DT) to hold the data. Then, perform the
setting so that the data can be transferred from DT to SV after the RUN mode starts.
2. Use the FP-e model with a battery.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Note 1)
AFPE224300
AFPE224305
(Standard type)
(Calendar timer
type)
Non-hold type: all points
From the set value to C139
C140 to C143, EV140 to EV143 (elapsed value)
Note 2)
SV: non-hold
SV: hold
976 points (R0 to R60F)
61 words (WR0 to WR60)
32 points (R610 to R62F)
2 words (WR61 to WR62)
1652 words (DT0 to DT1651)
8 words (DT1652 to DT1659)
AFPE214325
(Thermocouple input
type)
9-13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afpe224305Afpe224322Afpe224302Afpe214325

Table of Contents