Setting The Active Application; Configuring Communication Between Logic Editor And Logic Runtime - ABB COM600 3.4 User Manual

Station automation, logic processor
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

4.6.
4.7.
40
Station Automation COM600 3.4
Logic Processor User's Manual
6. Add a variable from the Available variables field to the Selected variables field,
select the variable and click the arrow button [>].
You can add all variables by clicking the double-arrow button [>>].
In this case, only signals that are used in this application are selected, i.e. tripping
signals: brk1SelectTrip, brk1Trip, brk2SelectTrip, brk2Trip, brk3SelectTrip, and
Brk3Trip; breaker failure of breaker 2: brk2Failure; reset from breaker 1
7. The access right for a selected item can be modified in the Selected variables field
by clicking the symbol in the Access Rights column.
During the compilation of the project, a symbol list is created, which gets exported
to a file (XML) in the project directory, and also gets loaded to the device during
the application download in the form of a child application.

Setting the active application

To set the active application:
1. Right-click the Main Task in the Devices window, and the editor view containing
the configuration of the task opens.
In the Devices window the name "Application" is displayed in bold letters. This
means that this application is set as "Active application". Thus all commands and
actions concerning the communication with the PLC refers to this application.
2. Click Add POU and the Input Assistant dialog opens.
3. In the Items tree view, select "PLC_BreakerFailureProtect" and click OK.
This program is added to main task.
4. In the Main Task Configuration dialog, set Priority to 0 and select Cyclic for the
task type and "t# 200ms" for 200-millisecond interval time.
Configuring communication between Logic Editor and
Logic Runtime
To configure a communication channel:
1. Double-click the device in the device window.
2. A dialog with the Communication Settings tab opens.
3. Select Gateway in the dialog and click Scan network to search for a device (PLC)
on COM600 in the local network.
The PLC found is displayed indented below the gateway.
4. Select the PLC (device) entry and click Set active path.
This sets the communication channel as the active one, which means that all actions
concerning the communication refers to this channel.