Control Terminal Programming Examples - GE AF-600 FP Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

About Programming
7.
AN-15 Terminal 53 High Ref./Feedb. Value. Set
maximum speed reference on Terminal 53 at 50
Hz. (This tells the adjustable frequency drive that
the maximum voltage received on Terminal 53
(10 V) equals 50 Hz output.)
Figure 5.7
With an external device providing a 0–10 V control signal
connected to adjustable frequency drive terminal 53, the
system is now ready for operation. Note that the scroll bar
on the right in the last figure of the display is at the
bottom, indicating the procedure is complete.
Figure 5.8 shows the wiring connections used to enable
this set-up.
Figure 5.8 Wiring Example for External Device Providing 0–10 V
Control Signal (Adjustable Frequency Drive Left, External Device
Right)
AF-600 FP Design and Installation Guide
5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
See Table 2.4 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in K-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Figure 5.9
2.
Figure 5.10
DET-768A
Each terminal has specified functions it is capable
of performing.
Parameters associated with the terminal enable
the function.
Press [Main Menu] twice, scroll to and press [OK].
Scroll to parameter group E-## Digital In/Out and
press [OK].
5
5
5-3