APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 59)
ADDR
REGISTER NAME
66D1
Underpower 1 Start Block Delay
66D2
Underpower 1 Alarm Power Pickup
66D3
Underpower 1 Alarm Pickup Delay
66D4
Underpower 1 Trip Power Pickup
66D5
Underpower 1 Trip Pickup Delay
66D6
Underpower 1 Trip Reset Delay
66D7
Underpower 1 Block
66D8
Underpower 1 Target
66D9
Underpower 1 Events
66DA
...Repeated for Underpower 2
Reduced Voltage Starting (Read/Write Grouped Setting)
67D0
Reduced Voltage Start Function
67D1
Reduced Voltage Start Transition Mode
67D2
Reduced Voltage Start FLA
67D3
Reduced Voltage Start Timer
67D4
Reduced Voltage Start Block
67D5
Reduced Voltage Start Target
67D6
Reduced Voltage Start Events
67D7
Reserved
Motor Acceleration Actuals (Read Only Non-Volatile) (5 modules)
6910
Motor Acceleration 1 Time/Date
6912
Motor Acceleration 1 Starting Time
6913
Motor Acceleration 1 Effective Current
6915
Motor Acceleration 1 Peak Current
6917
Reserved (9 items)
6920
...Repeated for Motor Acceleration 2
6930
...Repeated for Motor Acceleration 3
6940
...Repeated for Motor Acceleration 4
6950
...Repeated for Motor Acceleration 5
Motor Acceleration Commands (Read/Write Command)
6970
Motor Acceleration Clear Data Command
Motor Maximum Starting Rate (Read/Write Setting)
6980
Starts Per Hour Function
6981
Starts Per Hour Time Interval
6982
Starts Per Hour Maximum Number of Starts
6983
Starts Per Hour Block
6984
Starts Per Hour Target
6985
Starts Per Hour Events
6986
Reserved (9 items)
Motor Time Between Starts (Read/Write Setting)
6990
Time Between Starts Function
6991
Time Between Starts Minimum Time
6992
Time Between Starts Block
6993
Time Between Starts Target
6994
Time Between Starts Events
6995
Reserved (11 items)
Motor Restart Delay (Read/Write Setting)
69A0
Restart Delay Function
69A1
Restart Delay Minimum Time
69A2
Restart Delay Block
69A3
Restart Delay Target
69A4
Restart Delay Events
69A5
Reserved (11 items)
GE Multilin
RANGE
0 to 600
0.05 to 2
0 to 600
0.05 to 2
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 2
25 to 300
1 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 4294967295
0 to 655.35
0 to 999999.999
0 to 999999.999
---
0 to 1
0 to 1
1 to 300
1 to 16
0 to 65535
0 to 2
0 to 1
---
0 to 1
0 to 300
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 50000
0 to 65535
0 to 2
0 to 1
---
M60 Motor Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.01
F001
pu
0.01
F001
s
0.01
F001
pu
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F095
%
1
F001
s
0.1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F050
s
0.01
F001
A
0.001
F060
A
0.001
F060
---
---
F001
---
1
F126
---
1
F102
min
1
F001
---
1
F001
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
min
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
s
1
F001
---
1
F300
---
1
F109
---
1
F102
---
---
F001
DEFAULT
50
50
200
40
100
B
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (Current Only)
125
100
0
0 (Self-Reset)
0 (Disabled)
0
0
0
0
0
0
0 (No)
0 (Disabled)
60
3
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
20
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0
B-33