5.6 GROUPED ELEMENTS
g) TWO-SPEED MOTOR MAIN MENU

PATH: SETTINGS
GROUPED ELEMENTS
 TWO-SPEED MOTOR
The two-speed motor menu appears only if two-speed motor functionality is enabled in the

menu.
MOTOR
h) TWO-SPEED MOTOR THERMAL MODEL

PATH: SETTINGS
GROUPED ELEMENTS
SPEED2 THERMAL MODEL
 SPEED2 THERMAL
 MODEL
5
When two-speed motor functionality is used, these settings allow the selection of proper parameters for the thermal model
when motor is switched to the second speed. There is one thermal model in the M60, and it has inputs for overload condi-
tions from calculations at both speeds. As such, the accumulated thermal capacity is calculated from overload contributions
at each speed.
Refer to the Thermal model sub-section for details on settings for thermal model at the second motor speed.
5-136

SETTING GROUP 1(6)
 SPEED2 THERMAL
 MODEL
 SPEED2
MESSAGE
 ACCELERATION TIME
 SPEED2
MESSAGE
 UNDERCURRENT
SETTING GROUP 1(6)
SPEED2 THERMAL MODEL
CURVE: Motor
SPEED2 THERMAL MODEL
MESSAGE
TD MULTIPLIER: 1.00
SPEED2 VOLT DEPEND
MESSAGE
FUNCTION: Disabled
SPEED2 VOLT DEPEND
MESSAGE
MIN MOTOR VOLTS: 80%
SPEED2 VD VOLT LOSS:
MESSAGE
Off
SPEED2 VD STALL CURR
MESSAGE
@ MIN V: 4.50 x FLA
SPEED2 VD SAFE STALL
MESSAGE
TIME @ MIN V: 20.0 s
SPEED2 VD ACCL INSCT
MESSAGE
@ MIN V: 4.00 x FLA
SPEED2 VD STALL CURR
MESSAGE
@ 100%V: 6.00 x FLA
SPEED2 VD SAFE STALL
MESSAGE
TIME @ 100%V: 20.0 s
SPEED2 VD ACCL INSCT
MESSAGE
@ 100%V: 5.00 x FLA
M60 Motor Protection System

MOTOR
TWO-SPEED MOTOR
See page 5-136.
See page 5-137.
See page 5-138.

MOTOR
TWO-SPEED MOTOR
Range: Motor, FlexCurve A, FlexCurve B, FlexCurve C,
FlexCurve D, IEC
Range: 0.00 to 16.00 in steps of 0.01 when speed 2
thermal modle curve is Motor, otherwise 0.00 to
600.00 in steps of 0.01
Range: Disabled, Enabled
Range: 60 to 99% in steps of 1
Range: FlexLogic™ operand
Range: 1.50 to 20.00
Range: 0.1 to 1000.0 s in steps of 0.1
Range: 1.50 to 20.00
Range: 1.50 to 20.00
Range: 0.1 to 1000.0 s in steps of 0.1
Range: 1.50 to 20.00
5 SETTINGS

SETTINGS
SYSTEM SETUP
×
FLA in steps of 0.01
×
FLA in steps of 0.01
×
FLA in steps of 0.01
×
FLA in steps of 0.01