5 SETTINGS
c) UNDERPOWER

PATH: SETTINGS
GROUPED ELEMENTS
 UNDERPOWER
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Two underpower elements are provided.
The underpower function uses the source selected by the
Phase currents and voltages must configured on that source, otherwise the underpower function will not be functional. The
underpower element responds to total three-phase apparent power measured from the phase current and voltages.
When the underpower element is enabled, a trip or alarm are initiated once the magnitude of three-phase apparent power
falls below the pickup level for a period of time specified by the delay. For example, underpower may be used to detect
loss-of-load conditions. Loss of load conditions will not always cause a significant loss of current. Power is a more accurate
representation of loading and may be used for more sensitive detection of load loss or pump cavitations. This may be espe-
cially useful for detecting process related problems.
UNDERPOWER 1 START BLOCK DELAY: This setting specifies the length of time to block the underpower function
when motor is starting. If not in the starting state, the motor status is indicated by the
to the Motor setup section for additional information on using the
The underpower element is active only when the motor is running and is blocked upon the initiation of a motor start for
a period of time specified by this setting. For example, this block may be used to allow pumps to build up head before
the underpower element trips or alarms. A value of 0 specifies that the feature is not blocked from start. For values
other than 0, the feature is disabled when the motor is stopped and also from the time a start is detected until the time
entered expires.
UNDERPOWER 1 ALARM PWR PICKUP: This setting specifies a pickup threshold for the alarm stage. The base per-
unit power quantity is 3 × VT pu base × CT pu base per source selected as a motor line source. The alarm pickup
threshold should be less than the motor load current during normal operations.
UNDERPOWER 1 ALARM PICKUP DLY: This setting specifies a time delay for the alarm stage. The time delay
should long enough to overcome any short lowering of the current (for example, during system faults).
UNDERPOWER 1 TRIP PWR PICKUP: This setting specifies a pickup threshold for the trip stage. The base per-unit
power quantity is 3 × VT pu base × CT pu base per source selected as a motor line source. This setting should be less
than the corresponding setting for the alarm stage.
GE Multilin
SETTING GROUP 1(6)
POWER
UNDERPOWER 1
FUNCTION: Disabled
UNDERPOWER 1 START
BLOCK DLY:
0.50 s
UNDERPOWER 1 ALARM
PWR PICKUP: 0.50 pu
UNDERPOWER 1 ALARM
PICKUP DLY:
2.00 s
UNDERPOWER 1 TRIP
PWR PICKUP: 0.50 pu
UNDERPOWER 1 TRIP
PICKUP DLY:
1.00 s
UNDERPOWER 1 TRIP
RESET DLY:
1.00 s
UNDERPOWER 1 BLOCK:
Off
UNDERPOWER 1 TARGET:
Self-reset
UNDERPOWER 1 EVENTS:
Disabled
SYSTEM SETUP
MOTOR OFFLINE
M60 Motor Protection System
5.6 GROUPED ELEMENTS

UNDERPOWER
UNDERPOWER 1
Range: Enabled, Disabled
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.05 to 2.00 pu in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.05 to 2.00 pu in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Enabled, Disabled


MOTOR
MOTOR LINE SOURCE
MOTOR OFFLINE
operand for state determination.
5
setting.
operand. Refer
5-147