Teleprotection Channel Tests - GE M60 Instruction Manual

Motor protection system ur series
Hide thumbs Also See for M60:
Table of Contents

Advertisement

6.2 STATUS
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the fast EGD exchange is displayed.
b) SLOW EXCHANGE
PATH: ACTUAL VALUES
 SLOW EXCHANGE 1
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the slow EGD exchanges are displayed.
PATH: ACTUAL VALUES
 TELEPROT CH TESTS
6
The status information for two channels is shown here.
CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is "OK", teleprotection is
enabled and data is being received from the remote terminal; If the value is "FAIL", teleprotection enabled and data is
not being received from the remote terminal. If "n/a", teleprotection is disabled.
CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the

COMMANDS
CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
"FAIL" message will be displayed. The "N/A" value appears if the local relay ID is set to a default value of "0", the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
6-10

STATUS
EGD PROTOCOL STATUS
SLOW EXCHANGE 1
SIGNATURE:
SLOW EXCHANGE 1
MESSAGE
DATA LENGTH:

STATUS
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
MESSAGE
PACKETS:
CHANNEL 2
MESSAGE
STATUS: n/a
CHANNEL 2 LOST
MESSAGE
PACKETS:
VALIDITY OF CHANNEL
MESSAGE
CONFIGURATION: FAIL
menu.
M60 Motor Protection System

PRODUCER STATUS
SLOW EXCHANGE 1(2)
0
0

6.2.18 TELEPROTECTION CHANNEL TESTS

Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
6 ACTUAL VALUES
GE Multilin

Advertisement