GE N60 Instruction Manual page 459

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 62)
ADDR
REGISTER NAME
7841
Ohm Inputs 1 ID
7847
Ohm Inputs 1 Reserved (9 items)
7850
...Repeated for Ohm Inputs 2
Phasor Measurement Unit Power Trigger (Read/Write Setting) (4 modules)
7860
PMU 1 Power Trigger Function
7861
PMU 1 Power Trigger Active
7862
PMU 1 Power Trigger Reactive
7863
PMU 1 Power Trigger Apparent
7864
PMU 1 Power Trigger Pickup Time
7865
PMU 1 Power Trigger Dropout Time
7866
PMU 1 Power Trigger Block (3 items)
7869
PMU 1 Power Trigger Target
786A
PMU 1 Power Trigger Events
786B
...Repeated for PMU 2
7876
...Repeated for PMU 3
7881
...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting) (4 modules)
788C
PMU 1 Voltage Trigger Function
788D
PMU 1 Voltage Trigger Low Voltage
788E
PMU 1 Voltage Trigger High Voltage
788F
PMU 1 Voltage Trigger Pickup Time
7890
PMU 1 Voltage Trigger Dropout Time
7891
PMU 1 Voltage Trigger Block (3 items)
7894
PMU 1 Voltage Trigger Target
7895
PMU 1 Voltage Trigger Events
7896
...Repeated for PMU 2
78A0
...Repeated for PMU 3
78AA
...Repeated for PMU 4
Phasor Measurement Unit One-shot Command (Read/Write Setting)
78B4
PMU One-shot Function
78B5
PMU One-shot Sequence Number
78B6
PMU One-shot Time
Phasor Measurement Unit Test Values (Read/Write Setting) (4 modules)
78B8
PMU 1 Test Function
78B9
PMU 1 Phase A Voltage Test Magnitude
78BB
PMU 1 Phase A Voltage Test Angle
78BC
PMU 1 Phase B Voltage Test Magnitude
78BE
PMU 1 Phase B Voltage Test Angle
78BF
PMU 1 Phase C Voltage Test Magnitude
78C1
PMU 1 Phase C Voltage Test Angle
78C2
PMU 1 Auxiliary Voltage Test Magnitude
78C4
PMU 1 Auxiliary Voltage Test Angle
78C5
PMU 1 Phase A Current Test Magnitude
78C7
PMU 1 Phase A Current Test Angle
78C8
PMU 1 Phase B Current Test Magnitude
78CA
PMU 1 Phase B Current Test Angle
78CB
PMU 1 Phase C Current Test Magnitude
78CD
PMU 1 Phase C Current Test Angle
78CE
PMU 1 Ground Current Test Magnitude
78D0
PMU 1 Ground Current Test Angle
78D1
PMU 1 Test Frequency
78D3
PMU 1 Test df/dt
78D4
...Repeated for PMU 2
78F0
...Repeated for PMU 3
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
---
---
---
0 to 65535
---
1
0 to 1
---
1
0.25 to 3
pu
0.001
0.25 to 3
pu
0.001
0.25 to 3
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.25 to 1.25
pu
0.001
0.75 to 1.75
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 59
---
1
0 to 235959
---
1
0 to 1
---
1
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 700
kV
0.01
-180 to 180
°
0.05
0 to 9.999
kA
0.001
-180 to 180
°
0.05
0 to 9.999
kA
0.001
-180 to 180
°
0.05
0 to 9.999
kA
0.001
-180 to 180
°
0.05
0 to 9.999
kA
0.001
-180 to 180
°
0.05
20 to 70
Hz
0.001
-10 to 10
Hz/s
0.001
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F205
"Ohm Ip 1 "
F001
0
F102
0 (Disabled)
F001
1250
F001
1250
F001
1250
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
800
F001
1200
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
1
F050
0
F102
0 (Disabled)
F003
50000
F002
0
F003
50000
F002
-12000
F003
50000
F002
12000
F003
50000
F002
0
F004
1000
F002
-1000
F004
1000
F002
-13000
F003
1000
F002
11000
F004
0
F002
0
F003
60000
F002
0
B-37