APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 21 of 62)
ADDR
REGISTER NAME
Breaker Control (Read/Write Settings) (6 modules)
4700
Breaker 1 Function
4701
Breaker 1 Name
4704
Breaker 1 Mode
4705
Breaker 1 Open
4706
Breaker 1 Close
4707
Breaker 1 Phase A / Three-pole Closed
4708
Breaker 1 Phase B Closed
4709
Breaker 1 Phase C Closed
470A
Breaker 1 External Alarm
470B
Breaker 1 Alarm Delay
470D
Breaker 1 Pushbutton Control
470E
Breaker 1 Manual Close Recall Time
4710
Breaker 1 Out of Service
4711
Breaker 1 Block Open
4712
Breaker 1 Block Close
4713
Breaker 1 Phase A / Three-pole Opened
4714
Breaker 1 Phase B Opened
4715
Breaker 1 Phase C Opened
4716
Breaker 1 Operate Time
4717
Breaker 1 Events
4718
Reserved
4719
...Repeated for Breaker 2
4732
...Repeated for Breaker 3
474B
...Repeated for Breaker 4
4764
...Repeated for Breaker 5
477D
...Repeated for Breaker 6
Synchrocheck (Read/Write Setting) (2 modules)
47A0
Synchrocheck 1 Function
47A1
Synchrocheck 1 V1 Source
47A2
Synchrocheck 1 V2 Source
47A3
Synchrocheck 1 Maximum Voltage Difference
47A5
Synchrocheck 1 Maximum Angle Difference
47A6
Synchrocheck 1 Maximum Frequency Difference
47A7
Synchrocheck 1 Dead Source Select
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
47AA
Synchrocheck 1 Live V1 Minimum Voltage
47AB
Synchrocheck 1 Live V2 Minimum Voltage
47AC
Synchrocheck 1 Target
47AD
Synchrocheck 1 Events
47AE
Synchrocheck 1 Block
47AF
Synchrocheck 1 Frequency Hysteresis
47B0
...Repeated for Synchrocheck 2
Demand (Read/Write Setting)
47D0
Demand Current Method
47D1
Demand Power Method
47D2
Demand Interval
47D3
Demand Input
Demand (Read/Write Command)
47D4
Demand Clear Record
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 1
---
1
---
---
---
0 to 1
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65.535
s
0.001
0 to 1
---
1
0 to 65.535
s
0.001
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65.535
s
0.001
0 to 1
---
1
0 to 65535
s
1
0 to 1
---
1
0 to 5
---
1
0 to 5
---
1
0 to 400000
V
1
0 to 100
degrees
1
0 to 2
Hz
0.01
0 to 5
---
1
0 to 1.25
pu
0.01
0 to 1.25
pu
0.01
0 to 1.25
pu
0.01
0 to 1.25
pu
0.01
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 0.1
Hz
0.01
0 to 2
---
1
0 to 2
---
1
0 to 5
---
1
0 to 65535
---
1
0 to 1
---
1
0 to 65535
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F102
0 (Disabled)
F206
"Bkr 1"
F157
0 (3-Pole)
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F003
0
F102
0 (Disabled)
F003
0
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F001
70
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F167
1 (SRC 2)
F060
10000
F001
30
F001
100
F176
1 (LV1 and DV2)
F001
30
F001
30
F001
70
F001
70
F109
0 (Self-reset)
F102
0 (Disabled)
F300
0
F001
6
F139
0 (Thermal Exponentia
l)
F139
0 (Thermal Exponentia
l)
F132
2 (15 MIN)
F300
0
F126
0 (No)
F001
0
B-29