APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 60)
ADDR
REGISTER NAME
63C9
Reserved (8 items)
63D1
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 modules)
6440
Negative Sequence Overvoltage Function
6441
Negative Sequence Overvoltage Source
6442
Negative Sequence Overvoltage Pickup
6443
Negative Sequence Overvoltage Pickup Delay
6444
Negative Sequence Overvoltage Reset Delay
6445
Negative Sequence Overvoltage Block
6447
Negative Sequence Overvoltage Target
6448
Negative Sequence Overvoltage Events
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Phase Undervoltage (Read/Write Grouped Setting) (3 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7008
Phase Undervoltage 1 Target
7009
Phase Undervoltage 1 Events
700A
Phase Undervoltage 1 Measurement Mode
700B
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7047
Phase Overvoltage 1 Target
7048
Phase Overvoltage 1 Events
7049
Reserved (8 items)
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7200
Phase Directional Overcurrent 1 Function
7201
Phase Directional Overcurrent 1 Source
7202
Phase Directional Overcurrent 1 Block
7204
Phase Directional Overcurrent 1 ECA
7205
Phase Directional Overcurrent 1 Pol V Threshold
7206
Phase Directional Overcurrent 1 Block Overcurrent
7207
Phase Directional Overcurrent 1 Target
7208
Phase Directional Overcurrent 1 Events
7209
Reserved (8 items)
7211
...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7230
Neutral Directional Overcurrent 1 Function
7231
Neutral Directional Overcurrent 1 Source
7232
Neutral Directional Overcurrent 1 Polarizing
GE Multilin
RANGE
0 to 1
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 5
0 to 3
0 to 1
0 to 600
0 to 3
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 4294967295
0 to 359
0 to 3
0 to 1
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 2
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
0 (Definite Time)
s
0.01
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F300
degrees
1
F001
pu
0.001
F001
---
1
F126
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F230
DEFAULT
0
0 (Disabled)
0 (SRC 1)
B
300
50
50
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Phase to
Ground)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0
30
700
0 (No)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Voltage)