B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 24 of 60)
ADDR
REGISTER NAME
87L Power System In-Zone Transformer (Read/Write Setting)
4606
In-Zone Transformer Connection
4607
87L In-Zone Transformer Location
Breaker Control (Read/Write Settings) (2 modules)
47D0
Breaker 1 Function
B
47D1
Breaker 1 Name
47D4
Breaker 1 Mode
47D5
Breaker 1 Open
47D7
Breaker 1 Close
47D9
Breaker 1 Phase A / Three-pole Closed
47DB
Breaker 1 Phase B Closed
47DD
Breaker 1 Phase C Closed
47DF
Breaker 1 External Alarm
47E1
Breaker 1 Alarm Delay
47E3
Breaker 1 Pushbutton Control
47E4
Breaker 1 Manual Close Recall Time
47E6
Breaker 1 Out of Service
47E8
Breaker 1 Block Open
47EA
Breaker 1 Block Close
47EC
Breaker 1 Phase A / Three-pole Opened
47EE
Breaker 1 Phase B Opened
47F0
Breaker 1 Phase C Opened
47F2
Breaker 1 Operate Time
47F3
Breaker 1 Events
47F4
Reserved
47F5
...Repeated for Breaker 2
FlexCurves A and B (Read/Write Settings)
4910
FlexCurve A (120 items)
4988
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
Field Unit Raw Data Actuals (Read Only) (8 modules)
4E00
Raw Field Data AC1 Mag
4E02
Raw Field Data AC1 Angle
B-32
RANGE
0 to 12
0 to 2
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 1
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
---
0 to 65535
---
0 to 0.001
0 to 0.1
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F560
---
1
F562
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
---
1
F102
s
1
F001
ms
1
F011
ms
1
F011
---
1
F001
---
---
F202
---
---
F202
---
1
F001
---
---
F001
A
0.001
F003
degree
0.1
F002
DEFAULT
0 (None)
0 (Local-Tap)
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
0
0
70
0 (Disabled)
0
0
0
0
" "
" "
0
0
0
0