B.4 MEMORY MAPPING
Bitmask
Element
890
RTD Input 42
891
RTD Input 43
892
RTD Input 44
893
RTD Input 45
894
RTD Input 46
895
RTD Input 47
B
896
RTD Input 48
900
User-Programmable Pushbutton 1
901
User-Programmable Pushbutton 2
902
User-Programmable Pushbutton 3
903
User-Programmable Pushbutton 4
904
User-Programmable Pushbutton 5
905
User-Programmable Pushbutton 6
906
User-Programmable Pushbutton 7
907
User-Programmable Pushbutton 8
908
User-Programmable Pushbutton 9
909
User-Programmable Pushbutton 10
910
User-Programmable Pushbutton 11
911
User-Programmable Pushbutton 12
912
User-Programmable Pushbutton 13
913
User-Programmable Pushbutton 14
914
User-Programmable Pushbutton 15
915
User-Programmable Pushbutton 16
920
Disconnect switch 1
921
Disconnect switch 2
922
Disconnect switch 3
923
Disconnect switch 4
924
Disconnect switch 5
925
Disconnect switch 6
926
Disconnect switch 7
927
Disconnect switch 8
968
Breaker 1
969
Breaker 2
970
Breaker 3
971
Breaker 4
1012
Thermal overload protection 1
1013
Thermal overload protection 2
1014
Broken conductor detection 1
1015
Broken conductor detection 2
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
B-70
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F141
ENUMERATION: SELF TEST ERRORS
Bitmask
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
L30 Line Current Differential System
Error
Any Self Tests
IRIG-B Failure
Port 1 Offline
Port 2 Offline
Port 3 Offline
Port 4 Offline
Port 5 Offline
Port 6 Offline
RRTD Communications Failure
Voltage Monitor
FlexLogic Error Token
Equipment Mismatch
Process Bus Failure
Unit Not Programmed
System Exception
Latching Output Discrepancy
Ethernet Switch Fail
Maintenance Alert 01
SNTP Failure
---
Primary Ethernet Fail
Secondary Ethernet Fail
Temperature Monitor
Process Bus Trouble
Brick Trouble
Field RTD Trouble
APPENDIX B
GE Multilin