GE L30 Instruction Manual page 239

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
f) USER TRIGGERING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1 USER
 TRIGGER
The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is
refreshed once every two power system cycles.
g) FREQUENCY TRIGGERING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1 FREQUENCY
 TRIGGER
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from either phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the source
configuration as per L30 standards. This element requires the frequency is above the minimum measurable value. If the
frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
PMU 1 FREQ TRIGGER LOW-FREQ: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
PMU 1 FREQ TRIGGER HIGH-FREQ: This setting specifies the high threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
GE Multilin
Figure 5–32: STAT BITS LOGIC

PHASOR MEASUREMENT...
PMU1 USER TRIGGER:
Off

PHASOR MEASUREMENT...
PMU 1 FREQ TRIGGER
FUNCTION: Disabled
PMU 1 FREQ TRIGGER
LOW-FREQ: 49.00 Hz
PMU 1 FREQ TRIGGER
HIGH-FREQ: 61.00 Hz
PMU 1 FREQ TRIGGER
PKP TIME: 0.10 s
PMU 1 FREQ TRIGGER
DPO TIME: 1.00 s
PMU 1 FREQ TRIG BLK:
Off
PMU 1 FREQ TRIGGER
TARGET: Self-Reset
PMU 1 FREQ TRIGGER
EVENTS: Disabled
L30 Line Current Differential System


PMU 1 TRIGGERING
PMU 1 USER TRIGGER
Range: FlexLogic™ operands


PMU 1 TRIGGERING
PMU 1 FREQUENCY TRIGGER
Range: Enabled, Disabled
Range: 20.00 to 70.00 Hz in steps of 0.01
Range: 20.00 to 70.00 Hz in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Enabled, Disabled
5.4 SYSTEM SETUP
5
5-95

Advertisement

Table of Contents
loading