5 SETTINGS
C37.118 PMU 1 CONFIGURATION

PATH: SETTINGS
SYSTEM SETUP

RATION
37.118 PMU 1 CONFIGURATION
 37.118 PMU 1
 CONFIGURATION
MESSAGE
PMU 1 FORMAT: This setting selects whether synchrophasors are reported as 16-bit integers or 32-bit IEEE floating point
numbers. This setting complies with bit-1 of the FORMAT field of the IEEE C37.118 configuration frame. This setting
applies to synchrophasors only; the user-selectable FlexAnalog channels are always transmitted as 16-bit integer values.
PMU 1 STYLE: This setting selects whether synchrophasors are reported in rectangular (real and imaginary) coordinates
or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the IEEE C37.118
configuration frame.
With 90-5 PMU, the FORMAT and STYLE are Floating-point and Polar respectively, as specified in the IEC 61850
standard.
NOTE
IEC 61850–90–5 PMU 1 CONFIGURATION

PATH: SETTINGS
SYSTEM SETUP

TION
90 – 5 PMU 1 CONFIGURATION
 90–5 PMU 1
 CONFIGURATION
PMU1 LDINST: A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
LD.
As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64 charac-
ters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.
NOTE
c) AGGREGATORS

PATH: SETTINGS
PRODUCT SETUP
 PMU 1
 AGGREGATORS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
PMU AGGREGATOR1 IDCODE: This setting specifies an IDCODE for the aggregator. Individual PMU data streams
transmitted over this port are identified via their own IDCODES, as per the PMU IDCODE settings. This IDCODE is to
be used by the command frame to start/stop transmission, and request configuration.
GE Multilin

PHASOR MEASUREMENT
PMU 1 FORMAT:
Integer
PMU 1 STYLE:
Polar

PHASOR MEASUREMENT
PMU 1 LDINST:
PMU1

SYSTEM SETUP
PHASOR MEASUREMENT
PMU AGGREGATOR 1
PMU AGGREGATOR 1:
IDCODE: 1
PMU AGGREGATOR 1
PROTOCOL: None
AGGREGATOR1: TCP Port
NONE
AGGREGATOR1: UDP Port
NONE
PMU AGGREGATOR 1
PDC CONTROL: Disabled
PMU AGGREGATOR1
INCLUDE PMU1: No
L30 Line Current Differential System
BASIC CONFIGURATION
PMU 1
Range: Integer, Floating-point
Range: Polar, Rectangular
BASIC CONFIGURATION
PMU1
Range: 64 char ASCII text
PMU AGGREGATORS 1
Range: 1 to 65534 in steps of 1
Range: None, C37.118
Range: None, 4712, 4713, 4714, 4715, 4716, 4717,
4718, 4719
Range: None, 4712, 4713, 4714, 4715, 4716, 4717,
4718, 4719
Range: Disabled, Enabled
Range: No, Yes
5.4 SYSTEM SETUP
PMU 1 BASIC CONFIGU-
PMU 1 BASIC CONFIGURA-
5-91