GE L30 Instruction Manual page 517

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 57)
ADDR
REGISTER NAME
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
8601
Breaker Failure 1 Mode
8602
Breaker Failure 1 Source
8603
Breaker Failure 1 Amp Supervision
8604
Breaker Failure 1 Use Seal-In
8605
Breaker Failure 1 Three Pole Initiate
8606
Breaker Failure 1 Block
8607
Breaker Failure 1 Phase Amp Supv Pickup
8608
Breaker Failure 1 Neutral Amp Supv Pickup
8609
Breaker Failure 1 Use Timer 1
860A
Breaker Failure 1 Timer 1 Pickup
860B
Breaker Failure 1 Use Timer 2
860C
Breaker Failure 1 Timer 2 Pickup
860D
Breaker Failure 1 Use Timer 3
860E
Breaker Failure 1 Timer 3 Pickup
860F
Breaker Failure 1 Breaker Status 1 Phase A/3P
8610
Breaker Failure 1 Breaker Status 2 Phase A/3P
8611
Breaker Failure 1 Breaker Test On
8612
Breaker Failure 1 Phase Amp Hiset Pickup
8613
Breaker Failure 1 Neutral Amp Hiset Pickup
8614
Breaker Failure 1 Phase Amp Loset Pickup
8615
Breaker Failure 1 Neutral Amp Loset Pickup
8616
Breaker Failure 1 Loset Time
8617
Breaker Failure 1 Trip Dropout Delay
8618
Breaker Failure 1 Target
8619
Breaker Failure 1 Events
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
2 to 90
-55 to 125
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
0 to 1
0 to 1
0 to 65535
0 to 65535
0.001 to 30
0.001 to 30
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
0.001 to 30
0.001 to 30
0.001 to 30
0.001 to 30
0 to 65.535
0 to 65.535
0 to 2
0 to 1
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
C
1
F002
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F102
---
1
F157
---
1
F167
---
1
F126
---
1
F126
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
DEFAULT
0 (Disabled)
0 (SRC 1)
B
700
100
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
0
0
-55
125
0
0
0
0
0
0
0 (Disabled)
0 (3-Pole)
0 (SRC 1)
1 (Yes)
1 (Yes)
0
0
1050
1050
1 (Yes)
0
1 (Yes)
0
1 (Yes)
0
0
0
0
1050
1050
1050
1050
0
0
0 (Self-reset)
0 (Disabled)
B-43