5.4 SYSTEM SETUP
b) IN-ZONE TRANSFORMER

PATH: SETTINGS
SYSTEM SETUP
 IN-ZONE
 TRANSFORMER
The in-zone transformer settings described below ensure that the 87L element will correctly apply magnitude and phase
compensation for the in-zone transformer. To accommodate for the difference in CT ratios at line terminals, the

GROUPED ELEMENTS
setting should be used. It is important to properly program the in-zone transformer setting for all terminals to
DIFF CT TAP
ensure correct 87L performance.
IN-ZONE TRANSFORMER CONNECTION: This setting is used to indicate the presence and group connection of the
in-zone transformer. The winding angle selection specifies the phase shift of the remote terminal side winding with
respect to the local terminal side winding. For example, for the Dy1 group (delta winding connected to local terminal
side, and wye winding connected to remote terminal side), select the "30° lag" value for the local terminal side. If there
is no in-zone transformer connected, then program this setting as "None" (note that the "0° lag" value does not corre-
spond to "None"). Only one in-zone transformer is allowed for both two-terminal and three-terminal applications.
Enabling in-zone transformer functionality forces the L30 to automatically remove the zero-sequence component from
all terminals currents. It also disables ground differential 87LG functionality and zero-sequence current removal func-
tionality defined by the
TRANSFORMER LOCATION: This setting selects the transformer location and is applicable only if the
setting is not programmed as "None".
CONNECTION
5
Select the "LOCAL-TAP" value if the transformer is present between the local terminal and the tap point or for two-
terminal applications.
Select the "REM1-TAP" if the transformer is present between remote terminal 1 and the tap point.
Select the "REM2-TAP" if the transformer is present between remote terminal 2 and the tap point.
Figure 5–16: ILLUSTRATION OF IN-ZONE TRANSFORMER FOR TWO-TERMINAL AND THREE-TERMINAL LINES
5-70

87L POWER SYSTEM
IN-ZONE TRANSFORMER
CONNECTION: None
TRANSFORMER LOCATION:
MESSAGE
LOCAL-TAP
SETTING GROUP 1(6)
LINE DIFFERENTIAL ELEMENTS
ZERO SEQ CURRENT REMOVAL
L30 Line Current Differential System

IN-ZONE TRANSFORMER
Range: None, 0 to 330° lag in steps of 30°
Range: LOCAL-TAP, REM1-TAP, REM2-TAP
CURRENT DIFFERENTIAL
setting.
5 SETTINGS
SETTINGS

CURRENT
TRANSFORMER