Mounting Procedure For Flush Mounting - ABB RELION 670 Series Installation Manual

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 514 026-UEN B
5.3.1.2
670 series 2.2 IEC
Installation manual
1/2 x 19"
3/4 x 19"
1/1 x 19"
1/4 x 19" (RHGS6 6U)
Only a single case can be mounted in each cut-out on the cubicle panel, for class
IP54 protection. The screws from the IED shall be used to fasten the fasteners to
the IED.
Flush mounting cannot be used for side-by-side mounted IEDs
when IP54 class must be fulfilled. Only IP20 class can be obtained
when mounting two cases side-by-side in one (1) cut-out.
To obtain IP54 class protection, an additional factory mounted
sealing must be ordered when ordering the IED.

Mounting procedure for flush mounting

4
6
IEC16000080 V1 EN-US
Figure 3:
Flush mounting details.
3
2
IEC16000080=1=en.vsd
Section 5
Mounting
1
5
M11942-2 v5
23