Section 4
Unpacking, inspecting and storing
4.2.4
4.3
20
Returning an IED damaged in transit
If damage has occurred during transport, appropriate actions must be taken against
the latest carrier. Please inform the nearest ABB office or representative. Notify
ABB immediately if there are any discrepancies in relation to the delivery
documents.
Storing
Storing of the IED before installation must be done in the original transport
packaging in a dry and dust free place. Storage temperature must be within the
range of -40° C to +70° C. The average high temperature is recommended to be
less than +40° C, to minimize component ageing.
1MRK 514 026-UEN B
GUID-966A05ED-CD30-4F66-957E-00FF38943A73 v4
GUID-1DC9D33D-DC62-438B-9333-3BB354164CBC v7
670 series 2.2 IEC
Installation manual