Measured Value (Mv) - ABB COM600 User Manual

Station automation
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

IEC 60870-5-101
Master (OPC) 3.3
3.4.5.15.
40
Station Automation COM600
User's Manual
Property/ Para-
Value or Value range/ Default
meter
Common Data
LPL
Class
Vendor
Vendor
ABB
Software Revision
Software Revision
Description
Description

Measured value (MV)

Table 3.4.5.15-1 Configurable MV properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
MV
Class
Sub-Type
Sub Type
MW LIMITCHECK
MV Simple
Default: MV Simple
Addresses
Indication Address
0...16777215
Default: 0
Scale and Unit
Multiplier
Default: Deka
Scale
Lookup Table Scale
Stepwise Linear Scale
Default: None
Unit
Default: Dimensionless
Limit Value Super-
vision
Max
Default: 20000
Description
Common data class according to IEC
61850.
A simple text string, describing the vendor.
A simple text string, describing the soft-
ware revision.
A simple text string, describing the
description for logical node.
Description
Common data class according to IEC
61850.
Object subtype.
IEC address for indication.
Multiplier for measurement.
Scale for measurement.
Unit for measurement.
Maximum value for measurement.
1MRS756703