GE t60 Instruction Manual page 597

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 68 of 68)
ADDR
REGISTER NAME
EC03
Synchrocheck 1 Maximum Voltage Difference
EC05
Synchrocheck 1 Maximum Angle Difference
EC06
Synchrocheck 1 Maximum Frequency Difference
EC07
Synchrocheck 1 Dead Source Select
EC08
Synchrocheck 1 Dead V1 Maximum Voltage
EC09
Synchrocheck 1 Dead V2 Maximum Voltage
EC0A
Synchrocheck 1 Live V1 Minimum Voltage
EC0B
Synchrocheck 1 Live V2 Minimum Voltage
EC0C
Synchrocheck 1 Target
EC0D
Synchrocheck 1 Events
EC0E
Synchrocheck 1 Block
EC10
Synchrocheck 1 Frequency Hysteresis
EC11
...Repeated for Synchrocheck 2
EC22
...Repeated for Synchrocheck 3
EC33
...Repeated for Synchrocheck 4
Phasor Measurement Unit Frequency Trigger (Read/Write Setting) (4 modules)
ECCC
PMU 1 Frequency Trigger Function
ECCD
PMU 1 Frequency Trigger Low Frequency
ECCE
PMU 1 Frequency Trigger High Frequency
ECCF
PMU 1 Frequency Trigger Pickup Time
ECD0
PMU 1 Frequency Trigger Dropout Time
ECD1
PMU 1 Frequency Trigger Block (3 items)
ECD7
PMU 1 Frequency Trigger Target
ECD8
PMU 1 Frequency Trigger Events
Setting file template values (read only)
ED00
FlexLogic displays active
ED01
Undefined
ED07
Last settings change date
ED09
Template bitmask (750 items)
Phasor Measurement Unit Records (Read Only)
EFFF
PMU Recording Number of Triggers
GE Multilin
RANGE
0 to 400000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 4294967295
0 to 0.1
0 to 1
20 to 70
20 to 70
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
---
0 to 4294967295
0 to 65535
0 to 65535
T60 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
1 (LV1 and DV2)
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
---
1
F102
Hz
0.01
F001
Hz
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F205
---
1
F050
---
1
F001
samples
1
F001
DEFAULT
10000
30
100
30
B
30
70
70
0 (Self-reset)
0 (Disabled)
0
6
0 (Disabled)
4900
6100
10
100
0
0 (Self-reset)
0 (Disabled)
1 (Enabled)
(none)
0
0
0
B-75

Advertisement

Table of Contents
loading

Table of Contents