5.2 PRODUCT SETUP
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the T60 over a network. The T60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the T60 contains a list and description of all available files (event records, oscillography, etc.).
k) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 60870-5-104
 PROTOCOL
5
The T60 supports the IEC 60870-5-104 protocol. The T60 can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the T60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the T60 at one time.
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the T60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the T60 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the T60, the default thresholds are in effect.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to "Enabled", the DNP protocol does not operate. When this setting is changed, it takes effect when
power to the relay is cycled (off-to-on).
NOTE
l) EGD PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 EGD PROTOCOL
5-44

COMMUNICATIONS
IEC 60870-5-104
FUNCTION: Disabled
IEC TCP PORT
MESSAGE
NUMBER: 2404
 IEC NETWORK
MESSAGE
 CLIENT ADDRESSES
IEC COMMON ADDRESS
MESSAGE
OF ASDU:
IEC CYCLIC DATA
MESSAGE
PERIOD:
IEC CURRENT DEFAULT
MESSAGE
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
MESSAGE
THRESHOLD: 30000
IEC POWER DEFAULT
MESSAGE
THRESHOLD: 30000
IEC ENERGY DEFAULT
MESSAGE
THRESHOLD: 30000
IEC OTHER DEFAULT
MESSAGE
THRESHOLD: 30000
settings are used to determine when to trigger spontaneous responses containing

COMMUNICATIONS
 FAST PROD EXCH 1
 CONFIGURATION
 SLOW PROD EXCH 1
MESSAGE
 CONFIGURATION
 SLOW PROD EXCH 2
MESSAGE
 CONFIGURATION
T60 Transformer Protection System

IEC 60870-5-104 PROTOCOL
Range: Enabled, Disabled
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
0
Range: 1 to 65535 s in steps of 1
60 s
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
IEC CURRENT DEFAULT THRESHOLD

EGD PROTOCOL
5 SETTINGS