GE t60 Instruction Manual page 574

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 45 of 68)
ADDR
REGISTER NAME
993F
Reserved (2 items)
9941
...Repeated for breaker restrike 2
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9980
Teleprotection Clear Lost Packets
Teleprotection Inputs/Outputs (Read/Write Settings)
B
9990
Teleprotection Function
9991
Teleprotection Number of Terminals
9992
Teleprotection Number of Channels
9993
Teleprotection Local Relay ID
9994
Teleprotection Terminal 1 ID
9995
Teleprotection Terminal 2 ID
9996
Reserved (10 items)
9A00
Teleprotection Input 1-n Default States (16 items)
9A10
Teleprotection Input 2-n Default States (16 items)
9A20
Teleprotection Output 1-n Operand (16 items)
9A40
Teleprotection Output 2-n Operand (16 items)
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
9AA1
Teleprotection Channel 1 Number of Lost Packets
9AA2
Teleprotection Channel 2 Status
9AA3
Teleprotection Channel 2 Number of Lost Packets
9AA4
Teleprotection Network Status
9AAF
Teleprotection Channel 1 Input States
9AB0
Teleprotection Channel 2 Input States
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
Permissive overreach transfer trip (POTT) settings (read/write)
A070
POTT Scheme Function
A071
POTT Permissive Echo
A072
POTT Rx Pickup Delay
A073
POTT Transient Block Pickup Delay
A074
POTT Transient Block Reset Delay
A075
POTT Echo Duration
A076
POTT Line End Open Pickup Delay
A077
POTT Seal In Delay
A078
POTT Ground Direction OC Forward
A07A
POTT Rx
A07C
POTT Echo Lockout
A07D
POTT Target
A07E
Undefined
VT Fuse Failure (Read/Write Setting) (6 modules)
A09A
VT Fuse Failure Function
A09B
VT Fuse Failure Neutral Wire Open Function
A09C
VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
A0A6
...Repeated for module number 5
A0A9
...Repeated for module number 6
A0AC
VTFF x V0 3rd harmonic
Selector switch actual values (read only)
A210
Selector switch 1 position
A211
Selector switch 2 position
Selector switch settings (read/write, 2 modules)
B-52
RANGE
0 to 1
0 to 1
0 to 1
2 to 3
1 to 2
0 to 255
0 to 255
0 to 255
0 to 1
0 to 3
0 to 3
0 to 4294967295
0 to 4294967295
0 to 2
0 to 65535
0 to 2
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 2
0 to 2
0 to 1
0 to 1
0 to 3
0 to 999999.999
1 to 7
1 to 7
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F126
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F001
---
1
F086
---
1
F086
---
1
F300
---
1
F300
---
1
F134
---
1
F001
---
1
F134
---
1
F001
---
1
F134
---
1
F500
---
1
F500
---
1
F108
---
1
F108
---
1
F102
---
1
F102
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F300
s
0.001
F001
---
1
F109
---
1
F109
---
1
F102
---
1
F102
pu
0.001
F001
V
0.001
F060
---
1
F001
---
1
F001
DEFAULT
0
0 (No)
0 (Disabled)
2
1
0
0
0
0
0 (Off)
0 (Off)
0
0
1 (OK)
0
1 (OK)
0
2 (n/a)
0
0
0 (Off)
0 (Off)
0 (Disabled)
0 (Disabled)
0
20
90
100
50
400
0
0
250
0 (Self-reset)
0 (Self-reset)
0 (Disabled)
0 (Disabled)
100
0
0
1
GE Multilin