GE t60 Instruction Manual page 517

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 30 of 54)
ADDR
REGISTER NAME
86D9
Remote RTD 1 Alarm Temperature
86DA
Remote RTD 1 Alarm Pickup Delay
86DB
Remote RTD 1 Trip Temperature
86DC
Remote RTD 1 Trip Pickup Delay
86DD
Remote RTD 1 Trip Reset Delay
86DE
Remote RTD 1 Trip Voting
86DF
Remote RTD 1 Block
86E0
Remote RTD 1 Open
86E1
Remote RTD 1 Target
86E2
Remote RTD 1 Events
86E3
Repeatead for remote RTD input 2
86F6
Repeatead for remote RTD input 3
8709
Repeatead for remote RTD input 4
871C
Repeatead for remote RTD input 5
872F
Repeatead for remote RTD input 6
8742
Repeatead for remote RTD input 7
8755
Repeatead for remote RTD input 8
8768
Repeatead for remote RTD input 9
877B
Repeatead for remote RTD input 10
878E
Repeatead for remote RTD input 11
87A1
Repeatead for remote RTD input 12
Remote RTD inputs (Read Only Actual Values)
87C0
Remote RTD 1 Value
87C1
Remote RTD 2 Value
87C2
Remote RTD 3 Value
87C3
Remote RTD 4 Value
87C4
Remote RTD 5 Value
87C5
Remote RTD 6 Value
87C6
Remote RTD 7 Value
87C7
Remote RTD 8 Value
87C8
Remote RTD 9 Value
87C9
Remote RTD 10 Value
87CA
Remote RTD 11 Value
87CB
Remote RTD 12 Value
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
8A01
Digital Element 1 Name
8A09
Digital Element 1 Input
8A0A
Digital Element 1 Pickup Delay
8A0C
Digital Element 1 Reset Delay
8A0E
Digital Element 1 Block
8A0F
Digital Element 1 Target
8A10
Digital Element 1 Events
8A11
Digital Element 1 Pickup LED
8A12
Reserved (2 items)
8A14
...Repeated for Digital Element 2
8A28
...Repeated for Digital Element 3
8A3C
...Repeated for Digital Element 4
8A50
...Repeated for Digital Element 5
8A64
...Repeated for Digital Element 6
8A78
...Repeated for Digital Element 7
8A8C
...Repeated for Digital Element 8
GE Multilin
RANGE
1 to 200
5 to 600
1 to 200
5 to 600
5 to 600
0 to 13
0 to 65535
0 to 2
0 to 2
0 to 1
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
---
0 to 1
---
0 to 65535
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
0 to 1
---
T60 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
°C
1
F001
seconds
5
F001
°C
1
F001
seconds
5
F001
seconds
5
F001
---
1
F603
---
1
F300
---
1
F552
---
1
F109
---
1
F102
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
---
---
F300
---
1
F102
---
---
F203
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F001
DEFAULT
130
5
130
5
5
B
0 (None)
0
0 (None)
0 (Self-Reset)
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
"Dig Element 1"
0
0
0
0
0 (Self-reset)
0 (Disabled)
1 (Enabled)
0
B-37