Transformer - GE t60 Instruction Manual

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

6 ACTUAL VALUES
a) DIFFERENTIAL AND RESTRAINT CURRENTS
PATH: ACTUAL VALUES
METERING
DIFFERENTIAL AND
RESTRAINT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The metered differential current, restraint current, second harmonic current, and fifth harmonic current are displayed for
each phase. Refer to the Percent differential section in chapter 5 for details on how these values are calculated.
b) THERMAL ELEMENTS
PATH: ACTUAL VALUES
METERING
THERMAL
ELEMENTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin

TRANSFORMER

DIFFERENTIAL AND RESTRAINT
REFERENCE WINDING:
Winding 1
DIFF PHASOR Iad:
0.000 pu
0.0°
REST PHASOR Iar:
0.000 pu
0.0°
DIFF 2ND HARM Iad:
0.0% fo
0.0°
DIFF 5TH HARM Iad:
0.0% fo
0.0°
DIFF PHASOR Ibd:
0.000 pu
0.0°
REST PHASOR Ibr:
0.000 pu
0.0°
DIFF 2ND HARM Ibd:
0.0% fo
0.0°
DIFF 5TH HARM Ibd:
0.0% fo
0.0°
DIFF PHASOR Icd:
0.000 pu
0.0°
REST PHASOR Icr:
0.000 pu
0.0°
DIFF 2ND HARM Icd:
0.0% fo
0.0°
DIFF 5TH HARM Icd:
0.0% fo
0.0°
TRANSFORMER
THERMAL ELEMENTS
TOP OIL °C:
70°C
HOTTEST-SPOT °C:
130°
AGING FACTOR:
1.2
DAILY RATE LOL:
15 hrs
XFMR LIFE LOST:
100000 hrs
T60 Transformer Protection System
6.3 METERING
6.3.2 TRANSFORMER
6
6-13

Advertisement

Table of Contents
loading

Table of Contents