MODBUS MEMORY MAP
Address
Description
686C
Hybrid POTT 1P Trans Block Reset Delay
686D
Hybrid POTT 1P Echo Duration
686E
Hybrid POTT 1P Echo Lockout
686F
Hybrid POTT 1P Seal In Delay
6870
Hybrid POTT 1P Ground Directional Overcurrent
Forward
6871
Hybrid POTT 1P Gnd Directional Overcurrent Reverse 0 to 65535
6872
Hybrid POTT 1P Number of Communication Bits
6873
Hybrid POTT 1P Rx1
6874
Hybrid POTT 1P Rx2
6875
Hybrid POTT 1P Rx3
6876
Hybrid POTT 1P Rx4
6878
Hybrid POTT 1P Event
6879
Hybrid POTT 1P Echo Condition
687A
Hybrid POTT 1P Weak Infeed
687B
Hybrid POTT 1P Weak Infeed Condition
687C
Hybrid POTT 1P Block
687D
Reserved (3 items)
Pilot Blocking (1P) (Read/Write Setting)
6880
Blocking Scheme 1P Function
6881
Block 1P Rx Coord Pickup Delay
6882
Block 1P Transient Block Pickup Delay
6883
Block 1P Transient Block Reset Delay
6884
Blocking Scheme 1P Seal In Delay
6885
Blocking Scheme 1P Gnd Directional Overcurrent Fwd 0 to 65535
6886
Blocking Scheme 1P Gnd Directional Overcurrent Rev 0 to 65535
6887
Blocking Scheme 1P Number of Communication Bits 0 to 2
6888
Blocking Scheme 1P Rx1
6889
Blocking Scheme 1P Rx2
688A
Blocking Scheme 1P Rx3
688B
Blocking Scheme 1P Rx4
688D
Blocking 1P Event
688E
Blocking Scheme 1P Block
688F
Reserved (2 items)
Autoreclose 1P 3P (Read/Write Setting)
6890
Autoreclose Mode
6891
Autoreclose Maximum Number of Shots
6892
Autoreclose Block Breaker 1
6893
Autoreclose Close Time Breaker 1
6894
Autoreclose Breaker Manual Close
6895
Autoreclose Function
6896
Autoreclose Block Time Manual Close
6897
Autoreclose 1P Initiate
6898
Autoreclose 3P Initiate
6899
Autoreclose 3P TD Initiate
689A
Autoreclose Multi-Phase Fault
689B
Autoreclose Breaker 1 Pole Open
92
Range
Units
0 to 65.535
s
0 to 65.535
s
0 to 65.535
s
0 to 65.535
---
0 to 65535
---
---
0 to 2
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 1
---
0 to 65535
---
0 to 2
---
0 to 65535
---
0 to 65535
---
0 to 1
---
0 to 1
---
0 to 65.535
s
0 to 65.535
s
0 to 65.535
s
0 to 65.535
s
---
---
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 1
---
0 to 65535
---
0 to 1
---
0 to 3
---
1 to 4
---
0 to 65535
---
0 to 655.35
s
0 to 65535
---
0 to 1
---
0 to 655.35
s
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 2: MODBUS COMMUNICATION
Step
Format
Default
0.001
F001
90
0.001
F001
100
0.001
F001
250
0.001
F001
0
1
F300
0
1
F300
0
1
F198
0 (1)
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F102
0 (Disabled)
1
F300
0
1
F199
1 (Enabled)
1
F300
0
1
F300
0
1
F001
0
1
F102
0 (Disabled)
0.001
F001
10
0.001
F001
30
0.001
F001
90
0.001
F001
0
1
F300
0
1
F300
0
1
F198
0 (1)
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F102
0 (Disabled)
1
F300
0
1
F001
0
1
F080
3 (3 Pole-B)
1
F001
2
1
F300
0
0.01
F001
10
1
F300
0
1
F102
0 (Disabled)
0.01
F001
1000
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0