CHAPTER 2: MODBUS COMMUNICATION
Address
Description
41C3
Transient Record Trigger Position
41C4
Transient Record Sample Rate
41C5
Transient Record Analog Channel (16 items)
41E5
Transient Record Digital Channel (128 items)
4265
Transient Record Analog Channel High Trigger (16
items)
4275
Transient Record Analog Channel Low Trigger (16
items)
4285
Transient Record Digital Channel Trigger (128 items)
4305
Transient Record Analog Channel High Pickup (16
items)
4325
Transient Record Analog Channel Low Pickup (16
items)
4345
Transient Record Block Trigger
4346
Transient Record Analog Channel Block Trigger (16
items)
4356
Transient Record Maximum Retriggers
Installation (Read/Write Setting)
43E0
Relay Programmed State
43E1
Relay Name
43EB
User Configuration Name
43F5
User Configuration Date
Local/Remote (Read/Write Setting)
4438
Local Remote Function
4439
Local Remote PB Control
443A
Local Remote in Local
443B
Local Remote in Remote
443C
Local Remote Events
Local/Remote (Read/Write Command)
443D
Local Remote HMI Command
User-Programmable Self Tests (Read/Write Setting)
4443
Remote Device Off Function
4444
Ethernet Port 1 Fail Function
4445
Ethernet Port 2 Fail Function
4446
Ethernet Port 3 Fail Function
4447
SNTP Fail Function
4448
IRIG-B Fail Function
CT Settings (Read/Write Setting) (8 Modules)
4480
Phase CT 1 Ratio
4481
Phase CT 1 Secondary
4482
...Repeated for CT Bank 2
4484
...Repeated for CT Bank 3
4486
...Repeated for CT Bank 4
4488
...Repeated for CT Bank 5
448A
...Repeated for CT Bank 6
448C
...Repeated for CT Bank 7
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Units
1 to 100
%
0 to 5
---
0 to 4294967295
---
0 to 65535
---
0 to 3
---
0 to 3
---
0 to 3
---
0 to 1000000
---
0 to 1000000
---
0 to 65535
---
0 to 65535
---
1 to 4
---
0 to 1
---
---
---
---
---
0 to 4294967295
---
0 to 1
---
0 to 1
---
0 to 65535
---
0 to 65535
---
0 to 1
---
0 to 15
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
1 to 65000
---
0 to 1
---
MODBUS MEMORY MAP
Step
Format
Default
1
F001
50
1
F183
2 (32
samples/
cycle)
1
F600
0
1
F300
0
1
F094
0 (OFF)
1
F094
0 (OFF)
1
F094
0 (OFF)
0.1
F003
10000
0.1
F003
10000
1
F300
0
1
F300
0
1
F001
2
1
F133
0 (Not
Programmed)
---
F202
"0"
---
F202
"Initial"
1
F050
0
1
F102
0 (Disabled)
1
F102
1 (Enabled)
1
F300
0
1
F300
0
1
F102
1 (Enabled)
1
F107
0 (NONE)
1
F102
1 (Enabled)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
1
F102
1 (Enabled)
1
F102
1 (Enabled)
1
F001
1
1
F123
0 (1 A)
79