GE D90 Plus Communications Manual page 142

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

MODBUS MEMORY MAP
Address
Description
D0D4
Remote DPS Input 1 Name
D0DA
...Repeated for Remote DPS Input 2
D0E4
...Repeated for Remote DPS Input 3
D0EE
...Repeated for Remote DPS Input 4
D0F8
...Repeated for Remote DPS Input 5
D102
...Repeated for Remote DPS Input 6
D10C
...Repeated for Remote DPS Input 7
D116
...Repeated for Remote DPS Input 8
D120
...Repeated for Remote DPS Input 9
D12A
...Repeated for Remote DPS Input 10
D134
...Repeated for Remote DPS Input 11
D13E
...Repeated for Remote DPS Input 12
D148
...Repeated for Remote DPS Input 13
D152
...Repeated for Remote DPS Input 14
D15C
...Repeated for Remote DPS Input 15
D166
...Repeated for Remote DPS Input 16
IEC 61850 GGIO6 Configuration (Read/Write Setting)
D210
IEC 61850 GGIO6 Master Device (2 items)
D212
IEC 61850 GGIO6 Analog Value (4 items)
D21A
IEC 61850 GGIO6 Indication Operands (2 items)
IEC 61850 Report ConfRev (Read/Write Setting)
D260
IEC 61850 GGIO1 ConfRev
D262
IEC 61850 GGIO4 ConfRev
Mandatory (Read/Write Setting)
D280
Test Mode Function
D282
Test Mode Initiate
Mandatory (Read/Write Command)
D283
Clear All Relay Records Command
Contact Outputs (Read/Write Setting) (128 Modules)
D290
Contact Output 1 Name
D296
Contact Output 1 Operation
D297
Contact Output 1 Seal In
D298
Contact Output 1 Events
D299
Contact Output 1 Voltage Threshold
D29A
Contact Output 1 Reserved
D29B
...Repeated for Contact Output 2
D2A6
...Repeated for Contact Output 3
D2B1
...Repeated for Contact Output 4
D2BC
...Repeated for Contact Output 5
D2C7
...Repeated for Contact Output 6
D2D2
...Repeated for Contact Output 7
D2DD
...Repeated for Contact Output 8
D2E8
...Repeated for Contact Output 9
D2F3
...Repeated for Contact Output 10
D2FE
...Repeated for Contact Output 11
D309
...Repeated for Contact Output 12
138
Range
Units
---
---
0 to 32
---
0 to 4294967295
---
0 to 65535
---
1 to 4294967295
---
1 to 4294967295
---
0 to 1
---
0 to 65535
---
0 to 1
---
---
---
0 to 65535
---
0 to 65535
---
0 to 1
---
20 to 250
---
20 to 300
---
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 2: MODBUS COMMUNICATION
Step
Format
Default
---
F205
"RemDPS Ip
1"
1
F079
0 (NONE)
1
F600
0
1
F300
0
1
F003
1
1
F003
1
1
F102
0 (Disabled)
1
F300
1
1
F126
0 (No)
---
F205
"Cont Op 1"
1
F300
0
1
F300
0
1
F102
1 (Enabled)
1
F001
20
1
F001
125

Advertisement

Table of Contents
loading