PGC5000
PGC5000 Series Service Instructions
INDICATOR
ISSUE
Calibrating
Schedule running an
analysis on Calibration
Stream
Validating
Schedule runnign an
analysis on a Validation
Stream
Script Not Found
Script specified in TCF
cannot be located
Missing Report
Script cannot find the
report to be modified
Run Time
Script exceeded allotted
Exceeded
runtime
User Error #1 – 10
Script Asserts Error #1 – 10
Node Loss
Device no longer
reachable on SHS CANbus
New Node
Device added to SHS
CANbus
Address Conflict
Two devices with same
address on SHS CANbus
Invalid State
Combination of valve
states not allowed
Vol Flow Low Low
Volumetric Flow lower
than Low Low Limit
Vol Flow Low
Volumetric Flow lower
than Low Limit
Vol Flow High
Volumetric Flow exceeds
High Limit
Vol Flow High High
Volumetric Flow exceeds
High High Limit
Pressure Low Low
Pressure lower than Low
Low Limit
Pressure Low
Pressure lower than Low
Limit
Pressure High
Pressure exceeds High
Limit
Pressure High
Pressure exceeds High
High
High Limit
Temp Low Low
Temperature lower than
Low Low Limit
Temp Low
Temperature lower than
Low Limit
Temp High
Temperature exceeds High
Limit
Temp High High
Temperature exceeds High
High Limit
Vol Flow Low Low
Volumetric Flow lower
than Low Low Limit
Vol Flow Low
Volumetric Flow Lower
than Low Limit
SI/PGC5000-EN, Rev B
RESOLUTION (CHECK & CORRECT)
Information Only.
Information Only.
Ensure Script is in the Script library.
Edit the analysis under the Analysis
tab. Script tCF must have a time
greater than the analysis cycle time.
From Programming tab, check
script logic, increase Max Runtime
variable.
User programmable indicators.
Information Only.
Check cables and communication
path on SHS CANbus.
Information Only.
Check SHS Node ID on device.
Correct Valve conflicts.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
Information Only.
5 Diagnostics and troubleshooting
RESET
SOURCE
AOC
Schedule
AOC
Schedule
Next Run
Script
Next Run
Script
Next Run
Script
Next Run
Script
AOC
SHS
AOC
SHS
AOC
SHS
AOC
DVM
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
ARV
AOC
FastLoop
26