View Event Recordings; View Trip Values; Recalculate Distance To Fault; Trigger A Disturbance Report Manually - ABB REC670 Operator's Manual

Bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 8
Handle disturbances
8.2.3
8.2.4
8.2.5
8.3
38

View event recordings

The Event recording section in the Disturbance report shows the recording number.
The path in the HMI is shown below.
Main menu/Disturbance records/Record xx/Event recording

View trip values

In the Trip values section of a disturbance recording both the pre-fault and the fault
values for current, voltage and phase angle can be viewed. The recording number
and Trig time are also displayed. The path in the HMI is shown below.
Main menu/Disturbance records/Record xx/Trip Values

Recalculate distance to fault

This screen displays the fault loop with reactance and resistance values. To
recalculate the distance to fault, press the E key on the keypad.
In the Recalculate distance to fault section in a disturbance record it is possible not
only to view fault data but to recalculate the distance to a fault. By taking into
account peripheral influences like the resistance and reactance of other lines in the
immediate network area new distances can be calculated. The reactance and
resistance in the forward direction have the suffix B and in the reverse direction
they have the suffix A.
Recalculation may be necessary in cases where the data from a different fault loop
needs to be calculated. In three phase faults only one loop is shown in the
disturbance record. When recalculating, a different fault loop can be selected. The
path in the HMI is shown below.
Main menu/Disturbance records/Record xx/Recalc distance to fault

Trigger a disturbance report manually

Using the manual trigger generates an instant disturbance report. Use this function
to get a snapshot of the monitored line. Follow the path below and answer yes in
the Execute manual trig dialog box.
Main menu/Disturbance records/Manual trig
1MRK 511 188-UEN C
Operator's manual

Advertisement