Table 9. Electromagnetic compatibility tests
The EMC immunity test level meets the requirements listed below:
Description
1 MHz and 100 kHz burst disturbance test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency field immunity
Fast transient
• Power supply
• RJ-45 port
Surge immunity
• Power supply
Conducted radio frequency disturbance
Power frequency (50 Hz) magnetic field
Voltage dips and short interruptions
Emission tests
Table 10. Environmental conditions
Description
Operating temperature range
Relative humidity range, non-condensing
Storage temperature
1) Without any option cards
2) With Ethernet option card: 0...+55°C, with Serial option card: 0...+55°C
16
1MRS756764 D
Reference
According to IEC 61000-4-18
and IEC 60255-22-1
2.5 kV
1.0 kV
According to IEC 61000-4-2,
IEC 60255-22-2
6 kV
8 kV
According to IEC 61000-4-3
and IEC 60255-22-3
10 V/m (80% amp.mod.)
f=80...2700 MHz
10 V/m (pulse mod.) f=900
MHz
According to IEC 61000-4-4
and IEC 60255-22-4
2 kV
1 kV
According to IEC 61000-4-5
and IEC 60255-22-5
2 kV line-to-earth,
1 kV line-to-line
According to IEC 61000-4-6
and IEC 60255-22-6
10 V (80% ampl. mod.)
f= 150 kHz...80 MHz
According to IEC 61000-4-8,
300 A/m, continuous
According to IEC 61000-4-11
30% reduction for 10 ms
60% reduction for 100 ms
60% reduction for 1000 ms
>95% reduction for 5000 ms
According to EN 55011,
and IEC60255-25, class A
Value
-25...+70ºC
1) 2)
5...95% at +40ºC
-40...+70ºC